5.5KW 380V PLC Control Variable Frequency Inverter VSD AC Motor Drive Controller
1. Main features of K-DRIVE KD600S
1. Independent duct design, high quality cooling fan sinks the heat through the duct, prevents dust entering into PCB.
2. High speed accuracy and wide speed range.The inverter can run stably.
3. Big torque in low frequency, especially suitable for heavy duty industries.
4. Fast response to impact loads.
5. Three control modes:V/F, SVC, VC
6. Excellent SVC algorithm, stable operation in power generation..
7. Deceleration over exitation function.
8. Under voltage stall function
9. Thermal simulation testing platform.
10. Strict temperature rise test. It could run in hot areas and regions.
11. Complete protection with conformal coating.
12. IO expansion function And Powerful internal logic
13. Powerful debugging software.
14. Excellent speed tracking And Max 710KW Power
Model | Power Rating | Input Voltage | Output FREQ | Type |
---|---|---|---|---|
KD600S Series | 0.4kW-400kW | 208-240V / 380-480V ±10% | 0.00-3200.00Hz | DC/AC to AC inverters |
Thanks to sophisticated engineers, scientific producing workmanship, rigorous quality control systems and management team, K-Drive frequency inverters are equipped with advanced features, some of which are listed as below:
01. Starting torque: 180% at 0.5Hz (V/f pattern, SVC pattern);
02. Speed adjustable range: 1: 100 (V/f pattern, SVC pattern);
03. Speed accuracy: +/-0.5% (V/f pattern), +/-0.2% (SVC pattern);
04. Over load capability: 150% 1minute, 180% 10seconds;
05. Abundant frequency command sources;
06. Diverse input and output terminals;
07. Ambient temperature: -10°C~50°C;
08. High precise torque constraint, process PID control, multi-speed control, contracting brake control, field weakening control, all sides protection, etc;
09. Online and offline auto-tuning of motor parameters can both performed;
10. Extremely short-time acceleration can be performed without any trip, such as 0.1s or 0s from 0Hz to 50Hz;
Mains Supply (L1/L,L2,L3/N) | |
---|---|
Supply voltage | 208-240V ±10% 380-480V 690V ±10% |
Power source frequency | 50/60Hz ± 5% |
Displacement power factor (cos φ) | (>0.98) |
Output Data (U, V, W) | |
---|---|
Output voltage / frequency | 0-100% of supply voltage / 0.00-600.00Hz or customized |
Ramp time | 0.01-60000s |
Note: 150% current can be provided for 1 minute, 180% for 10 seconds. Higher overload rating is achieved by oversizing the drive.
Digital Input | |
---|---|
Programmable digital inputs | 5 |
Logic | NPN or PNP |
Voltage level | 22 - 26V |
Analog Input | |
Analog inputs | 2 |
Modes | Voltage or current |
Level | 0 to +10V, 0/4 to 20 mA (scalable) |
Automatic correction | YES |
Relay Output | |
Programmable relay outputs | 1 |
RA - RB / TA - TB | Normally close |
RA - RC / TA - TC | Normally open |
Contact capacitance | 250 V AC / 3A, 30 V DC / 3 A |
Terminal 485 Interface | |
485+ / 485- | Rate: 4800/9600/19200/38400/57600/115200 bps Max. distance: 500 m |
GND | Isolated from COM |
Ambient | |
Vibration | Less than 5.9 m/s² (0.6g) |
Humidity | Relative humidity 5% - 95 %. No condensation |
Corrosive environment | 3C3 |
Ambient temperature | -10 ºC - 50 ºC |
Altitude | 0 - 2,000 m |
Rated output current derated 1% every 100 m above 1,000 m | |
Storage temperature | -40 - +70 ºC |
Efficiency | Efficiency At rated amps: ≥93% |
IP grade | IP20 |
Cooling method | Forced air cooling |
Fieldbus Communication | |
Modbus RTU, Modbus ASCII | Built-in |
Production
In production, rigorous quality control is implemented on components, circuit boards, and the finished goods, assuring products without defects.
Performance | Common brands | K-Drive |
---|---|---|
Applicable motors | Asynchronous motors | Asynchronous /synchronous motors |
Starting torque | 2.0Hz, 150% (sensor-less vector control) 0Hz, 180% (closed-loop vector control) | 0.5Hz, 180% (sensor-less vector control) 0Hz, 200% (closed-loop vector control) |
Speed adjustable range | 1:100 (SVC), 1:1000 (VC) | 1:200 (SVC), 1:1000 (VC) |
Ambient temperature (no derating required) | -10-40ºC | -10-50ºC (for most of the models) |
Rated input voltage | 208VAC-400VAC | 208VAC-480VAC |
Communication | Modbus RTU//ASCII | Modbus RTU//ASCII Profibus-DP, CANopen, etc. |
Position control (fixed length, or angular positioning) | × | √ |
Field weakening control | × | √ |
Autotune online | Online | Online & Offline |
Short-time ramp-up | Trip | No trip |
Customized features (software and/or hardware) | Unprocurable or no experience | Procurable with rich experience |